액화석유가스(LPG) 충전사업시설의 위험성 평가분석
Liquefied Petroleum Gas Charging Facility Risk Assessment
공하성(우석대학교); 이재옥(목원대학교 소방방재학과)
27권 1호, 33~41쪽
초록
This study aims to quantitatively evaluate the potential risks that may occur in liquefied petroleum gas (LPG) filling and storage facilities, to analyze the impact on the human body and surrounding buildings in the event of an accident, and to suggest safety measures. The range of damage from overpressure and radiant heat was estimated through ALOHA simulation. In the case of overpressure, damage occurred within a radius of 140 m for both scenarios at 8 psi, 141–191 m for 3.5 psi, and 192–408 m for 1 psi. Radiant heat affected up to 1.7 km for a large storage volume of 220.5 tons, and up to 1.6 km for 180 tons. It was confirmed that the damage radius tended to expand as the storage volume increased. This suggested the need to secure a minimum safety distance, strengthen fire resistance, and establish an emergency response system.
Abstract
This study aims to quantitatively evaluate the potential risks that may occur in liquefied petroleum gas (LPG) filling and storage facilities, to analyze the impact on the human body and surrounding buildings in the event of an accident, and to suggest safety measures. The range of damage from overpressure and radiant heat was estimated through ALOHA simulation. In the case of overpressure, damage occurred within a radius of 140 m for both scenarios at 8 psi, 141–191 m for 3.5 psi, and 192–408 m for 1 psi. Radiant heat affected up to 1.7 km for a large storage volume of 220.5 tons, and up to 1.6 km for 180 tons. It was confirmed that the damage radius tended to expand as the storage volume increased. This suggested the need to secure a minimum safety distance, strengthen fire resistance, and establish an emergency response system.
- 발행기관:
- 대한안전경영과학회
- 분류:
- 안전공학