PyroSim을 활용한 차동식 스포트형 감지기의 부착높이별 작동시간 분석

A PyroSim Based Study on the Influence of Installation Height on the Activation Time of Rate-of-Rise Spot-Type Heat Detectors

김주성(우석대학교 일반대학원 소방방재학과); 공하성(우석대학교)

27권 3호, 71~78쪽

초록

This study quantitatively analyzed the effect of ceiling height on the response time of rate of rise heat detectors. A 7 m × 5 m simulation model was constructed using the PyroSim program, and scenarios were conducted by varying the installation height from 4.0 m to 7.5 m in 0.5 m increments. A wooden pallet fire source, placed at a height of 1.22 m, was simulated. The simulation results showed that as the installation height increased, the response time was delayed from 155.6 seconds to 204.6 seconds a difference of approximately 49 seconds. Meanwhile, the activation temperature decreased from 50.4 ℃ to 43.4 ℃, representing a drop of about 7 ℃. These findings indicate that in structures with higher ceilings, the responsiveness of detectors may be compromised due to the delayed arrival of hot air flows. Therefore, current height based installation standards in prescriptive design should be re-evaluated for high ceiling structures. Complementary design measures such as optimized placement, detector type selection, and increased installation density are recommended.

Abstract

This study quantitatively analyzed the effect of ceiling height on the response time of rate of rise heat detectors. A 7 m × 5 m simulation model was constructed using the PyroSim program, and scenarios were conducted by varying the installation height from 4.0 m to 7.5 m in 0.5 m increments. A wooden pallet fire source, placed at a height of 1.22 m, was simulated. The simulation results showed that as the installation height increased, the response time was delayed from 155.6 seconds to 204.6 seconds a difference of approximately 49 seconds. Meanwhile, the activation temperature decreased from 50.4 ℃ to 43.4 ℃, representing a drop of about 7 ℃. These findings indicate that in structures with higher ceilings, the responsiveness of detectors may be compromised due to the delayed arrival of hot air flows. Therefore, current height based installation standards in prescriptive design should be re-evaluated for high ceiling structures. Complementary design measures such as optimized placement, detector type selection, and increased installation density are recommended.

발행기관:
대한안전경영과학회
분류:
안전공학

AI 법률 상담

이 논문의 주제에 대해 더 알고 싶으신가요?

460만+ 법률 자료에서 관련 판례·법령·해석례를 찾아 답변합니다

AI 상담 시작
PyroSim을 활용한 차동식 스포트형 감지기의 부착높이별 작동시간 분석 | 대한안전경영과학회지 2025 | AskLaw | 애스크로 AI