부착높이에 따른 정온식 감지기의 작동 시간 분석

Activation Time Analysis of Fixed-Temperature Heat Detectors with Respect to Installation Height

김주성(우석대학교 일반대학원 소방방재학과); 공하성(우석대학교)

27권 3호, 79~87쪽

초록

The Pyrosim fire simulation program was used to investigate changes in operating time as a function of the attachment height of a fixed-temperature detector. Operating times were analyzed for detector heights ranging from 4 m to 7.5 m, in 0.5 m increments, within a 30 m2 space. The fire source was modeled as a wooden pallet 1.22 m in height, and a Type 1 fixed-temperature detector with an activation temperature of 67.9℃ was used. The simulation results showed that operating time increased progressively with detector height, rising from 155.7 seconds at 4m to 206.3 seconds at 7.5 m a maximum delay of 50.6 seconds. Notably, larger increases were observed in the 4 m ~ 4.5 m and 6 m ~ 6.5 m ranges 14.9 and 11.5 seconds, respectively than those observed in other intervals. This suggests that critical height ranges should be considered when establishing detector installation standards. This study found that current design standards may not ensure adequate detection performance in high-ceilinged structures. In warehouses and industrial facilities with ceilings of 6m or higher, such delays in detector activation could hinder early detection, indicating a need for improvements

Abstract

The Pyrosim fire simulation program was used to investigate changes in operating time as a function of the attachment height of a fixed-temperature detector. Operating times were analyzed for detector heights ranging from 4 m to 7.5 m, in 0.5 m increments, within a 30 m2 space. The fire source was modeled as a wooden pallet 1.22 m in height, and a Type 1 fixed-temperature detector with an activation temperature of 67.9℃ was used. The simulation results showed that operating time increased progressively with detector height, rising from 155.7 seconds at 4m to 206.3 seconds at 7.5 m a maximum delay of 50.6 seconds. Notably, larger increases were observed in the 4 m ~ 4.5 m and 6 m ~ 6.5 m ranges 14.9 and 11.5 seconds, respectively than those observed in other intervals. This suggests that critical height ranges should be considered when establishing detector installation standards. This study found that current design standards may not ensure adequate detection performance in high-ceilinged structures. In warehouses and industrial facilities with ceilings of 6m or higher, such delays in detector activation could hinder early detection, indicating a need for improvements

발행기관:
대한안전경영과학회
분류:
안전공학

AI 법률 상담

이 논문의 주제에 대해 더 알고 싶으신가요?

460만+ 법률 자료에서 관련 판례·법령·해석례를 찾아 답변합니다

AI 상담 시작
부착높이에 따른 정온식 감지기의 작동 시간 분석 | 대한안전경영과학회지 2025 | AskLaw | 애스크로 AI